4.h.
Special Magistrate Ross Hearing
- Meeting Date:
- 02/15/2017
- Re
- Case #16-2208 - 907 Citrus Ave
- Submitted For:
- Shaun Coss
Information
SUBJECT:
| 16-2208 | 907 Citrus Ave | Mulgrew, Shane | Shaun Coss |
CASE INFORMATION:
| Case Initiated: | September 16, 2016 | Type of Presentation: | Regular |
OWNER:
| OWNER: Shane Mulgrew 214 Southern Ave Fort Pierce, FL 34950 |
OCCUPIED BY: |
VIOLATIONS:
Section(s): 5-1.101.2.1 Unsafe Building
IPMC 108.1.1 Unsafe Structure
IPMC 108.1.3 Structure Unfit for Human Occupancy
IPMC 304.13 Windows, Doors & Frames
IPMC 304.13.1 Glazing
IPMC 305.3 Interior Surfaces
IPMC 305.4 Walking Surfaces
IPMC 309.1 Infestation
IPMC 403.2 Bathrooms & Toilet Room Privacy
IPMC 504.1 Plumbing Fixtures
IPMC 506.2 Sanitary Drainage System Maintenance
IPMC 602.2 Residential Heat Supply
IPMC 605.1 Electrical Equipment
IPMC 6052 Electrical Receptacles
IPMC 704.2.1 Smoke Alarms
IPMC 108.1.1 Unsafe Structure
IPMC 108.1.3 Structure Unfit for Human Occupancy
IPMC 304.13 Windows, Doors & Frames
IPMC 304.13.1 Glazing
IPMC 305.3 Interior Surfaces
IPMC 305.4 Walking Surfaces
IPMC 309.1 Infestation
IPMC 403.2 Bathrooms & Toilet Room Privacy
IPMC 504.1 Plumbing Fixtures
IPMC 506.2 Sanitary Drainage System Maintenance
IPMC 602.2 Residential Heat Supply
IPMC 605.1 Electrical Equipment
IPMC 6052 Electrical Receptacles
IPMC 704.2.1 Smoke Alarms
CORRECTIVE ACTIONS:
1. Install smoke alarms as required.
2. Replace damaged and missing faceplates on electrical outlets and switches.
3. Install door sweeps and weather stripping on both exterior doors.
4. Replace all broken window glazing.
5. Repair or replace all damaged window hardware.
6. Have the property treated for the infestation of roaches, rats and termites.
7. Eliminate the exposed electric in the front room, electrical tape is not an appropriate safeguard.
8. Repair or replace the ventilation fan in the bathrooms.
9. Seal all holes in the walls and ceilings to prevent the entry of insects and rodents.
10. Heat is required in the structure, replace the HVAC system.
11. Repair the leaking piping in the laundry room.
12. Replace broken tiles. They pose a tripping hazard and the sharp edges are also hazardous.
13. Replace all sagging or otherwise damaged acoustical ceiling tiles. Repair or replace the framing for the acoustical ceiling if
necessary.
2. Replace damaged and missing faceplates on electrical outlets and switches.
3. Install door sweeps and weather stripping on both exterior doors.
4. Replace all broken window glazing.
5. Repair or replace all damaged window hardware.
6. Have the property treated for the infestation of roaches, rats and termites.
7. Eliminate the exposed electric in the front room, electrical tape is not an appropriate safeguard.
8. Repair or replace the ventilation fan in the bathrooms.
9. Seal all holes in the walls and ceilings to prevent the entry of insects and rodents.
10. Heat is required in the structure, replace the HVAC system.
11. Repair the leaking piping in the laundry room.
12. Replace broken tiles. They pose a tripping hazard and the sharp edges are also hazardous.
13. Replace all sagging or otherwise damaged acoustical ceiling tiles. Repair or replace the framing for the acoustical ceiling if
necessary.
RECOMMENDATION:
The City requests that if the Special Magistrate finds the violation exists, the violator(s) be given 60 days to obtain a permit and comply with all permit conditions or a fine of $100.00 per day be assessed.
Form Review
- Form Started By:
- Shaun Coss
- Started On:
- 01/13/2017 03:56 PM
- Final Approval Date:
- 02/10/2017